Call us 24/7+86 18250705533
HONG KONG SAUL ELECTRICAL LIMITED! Email:sales5@xrjdcs.com Whatsapp:+86 18250705533

HIMA F6705 2-Channel Analog Output Module Current Signal 4-20mA

  • The HIMA F6705 is a galvanically isolated DC/DC converter module for HIMA H41q/H51q safety control racks. It converts 24 V DC input to a regulated 5 V DC output (10 A rated), powering central processors, I/O logic, and communication modules within the safety instrumented system.
  • The HIMA F6705 is a rack-mounted, galvanically isolated DC/DC safety power supply module designed for the central rack of HIMA H41q / H51q safety-related control systems (PES). It converts a 24 V DC primary supply into a tightly regulated 5 V DC system voltage that powers the central processing units, communication modules, and I/O logic circuits inside the safety instrumented system (SIS) rack.

🔷Key Specifications

Specification
Detail
Brand
HIMA
Model
F6705
Module Type
Isolated DC/DC Safety Power Supply Module
Compatible System
HIMA PES H41q / H51q Safety Control Systems
Input Voltage
24 V DC (range –15 % to +20 %)
Output Voltage
5 V DC, stepless adjustable; factory preset 5.4 V DC ±0.025 V
Rated Output Current
10 A continuous
Current Limiting
Approx. 13 A
Overvoltage Protection
6.5 V DC ±0.5 V
Isolation
Galvanic isolation between 24 V input and 5 V output
Conversion Efficiency
≥ 77 %
Front Panel
Test socket + voltage trim potentiometer
Redundancy
Supports parallel redundant operation (voltage balance ≤ 0.025 V between modules)
Rack Width
8 TE (standard F-series plug-in format)
Operating Temp.
–20 °C to +60 °C
Storage Temp.
–40 °C to +85 °C
Humidity
5 %–95 % RH, non-condensing
Protection
Overvoltage, overcurrent, short-circuit proof
Safety Integrity
SIL 3 capable (IEC 61508 / IEC 61511 context)
EMC Compliance
VDE 0871 / 0877 Class B
Country of Origin
Germany

🔨Product Overview

The HIMA F6705 is the dedicated 24 VDC-to-5 VDC converter module for HIMA safety racks. Unlike a commercial off-the-shelf power supply, it is qualified for use in safety-related automation architectures where deterministic fault behavior, electrical isolation, and redundant availability are mandatory.
Installed in the central rack backplane, the F6705:
  • Supplies regulated 5 V DC to H41q/H51q central modules and I/O carriers
  • Electrically isolates field-side 24 V DC from sensitive 5 V logic circuits
  • Detects overvoltage, overload, and short-circuit conditions
  • Supports load-sharing redundancy with other F6705 modules
Because the module is part of the safety power architecture, a single F6705 failure in a redundant setup does not disable the safety function. The remaining module continues to carry the 5 V backplane load while the fault is reported to the controller.
HIMA F6705 2-Channel Analog Output Module Current Signal 4-20mA HIMA F6705 2-Channel Analog Output Module Current Signal 4-20mA HIMA F6705 2-Channel Analog Output Module Current Signal 4-20mA




    Customers reviews