HIMA F8628X PROFIBUS DP Slave Communication Interface Module

  • The HIMA F8628X is a galvanically isolated DC/DC converter module for HIMA H41q/H51q safety control racks. It converts 24 V DC input to a regulated 5 V DC output (10 A rated), powering central processors, I/O logic, and communication modules within the safety instrumented system.
  • The HIMA F8628X is a rack-mounted, galvanically isolated DC/DC safety power supply module designed for the central rack of HIMA H41q / H51q safety-related control systems (PES). It converts a 24 V DC primary supply into a tightly regulated 5 V DC system voltage that powers the central processing units, communication modules, and I/O logic circuits inside the safety instrumented system (SIS) rack.

🔷Key Specifications

Specification
Detail
Brand
HIMA
Model
F8628X
Module Type
Isolated DC/DC Safety Power Supply Module
Compatible System
HIMA PES H41q / H51q Safety Control Systems
Input Voltage
24 V DC (range –15 % to +20 %)
Output Voltage
5 V DC, stepless adjustable; factory preset 5.4 V DC ±0.025 V
Rated Output Current
10 A continuous
Current Limiting
Approx. 13 A
Overvoltage Protection
6.5 V DC ±0.5 V
Isolation
Galvanic isolation between 24 V input and 5 V output
Conversion Efficiency
≥ 77 %
Front Panel
Test socket + voltage trim potentiometer
Redundancy
Supports parallel redundant operation (voltage balance ≤ 0.025 V between modules)
Rack Width
8 TE (standard F-series plug-in format)
Operating Temp.
–20 °C to +60 °C
Storage Temp.
–40 °C to +85 °C
Humidity
5 %–95 % RH, non-condensing
Protection
Overvoltage, overcurrent, short-circuit proof
Safety Integrity
SIL 3 capable (IEC 61508 / IEC 61511 context)
EMC Compliance
VDE 0871 / 0877 Class B
Country of Origin
Germany

🔨Product Overview

The HIMA F8628X is the dedicated 24 VDC-to-5 VDC converter module for HIMA safety racks. Unlike a commercial off-the-shelf power supply, it is qualified for use in safety-related automation architectures where deterministic fault behavior, electrical isolation, and redundant availability are mandatory.
Installed in the central rack backplane, the F8628X:
  • Supplies regulated 5 V DC to H41q/H51q central modules and I/O carriers
  • Electrically isolates field-side 24 V DC from sensitive 5 V logic circuits
  • Detects overvoltage, overload, and short-circuit conditions
  • Supports load-sharing redundancy with other F8628X modules
Because the module is part of the safety power architecture, a single F8628X failure in a redundant setup does not disable the safety function. The remaining module continues to carry the 5 V backplane load while the fault is reported to the controller.
HIMA F8628X PROFIBUS DP Slave Communication Interface Module HIMA F8628X PROFIBUS DP Slave Communication Interface Module HIMA F8628X PROFIBUS DP Slave Communication Interface Module




    Customers reviews

    There are no reviews yet.

    Be the first to review “HIMA F8628X PROFIBUS DP Slave Communication Interface Module”

    Ваш адрес email не будет опубликован. Обязательные поля помечены *

    wechat

    whatsapp

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8618250705533
    email: sales5@xrjdcs.com